Operating Instruction
72
BUSARBIT-DIAG.
0
Diagnostics: Bus arbitation (this pump)
S U B M E N U
RS 485-Interface
SUBMENU Serial Interface; to entry push
[ ] at least 1 sec..
PUMP-ADDRESS
OFF
SIO-Address of the pump
ADC REFERENCE
Local
Actual value or frequency reference enabled by the
local ADC or by SIO
FREQU. – LIFTING
37 Hz
Frequency limit for desired value lift
LIFT – AMOUNT
0.0 %
Lift amount in % of desired value point
(at maximum frequency)
ANALOG – OUT
Actual value
Meter output: ACTUAL FREQUENCY
(corresp. to max. output frequency);
ACTUAL VALUE (corresp. to max. desired pressure)
DIMENSION UNIT
psi
Displayed dimension unit
TEST RUN
after 100 h.
Time interval for test run
(10...100h...deactivated [ + ])
S U B M E N U
TEST RUN man.
SUBMENU Pump test run manual; to entry push [
]
at least 1 sec..
TEST RUN man
+
Start test – run with [ + ]
TEST-FREQUENCY
30.0 Hz
Test – run frequency
BOOST TEST-RUN
10 %
Test – run boost
S U B ME N U
ERRORS
SUBMENU Errors: to entry push [ ] at least 1 sec.
CONVEYOR-LIMIT
Disabled
Conveyor limit: In case fall short of turn off